ISO IEC 11801-5 pdf download

admin
ISO IEC 11801-5 pdf download

ISO IEC 11801-5 pdf download.INFORMATION TECHNOLOGY – GENERIC CABLING FOR CUSTOMER PREMISES – Part 5: Data centres
1 Scope
This part of ISO/IEC 1 1 801 specifies generic cabling within and to the computer room spaces of data centre premises, or data centre spaces within other types of buildings. It covers balanced cabling and optical fibre cabling. This document is optimized for premises in which the maximum distance over which telecommunications services can be distributed is 2 000 m. The principles of this document can also be applied to larger installations. Cabling specified by this document supports a wide range of services including voice, data and video that can also incorporate the supply of power. This document specifies directly or via reference to ISO/IEC 1 1 801 -1 a) the structure and minimum configurations for generic cabling within data centres, b) the interfaces at the equipment outlet (EO) and the external network interface (ENI), c) the performance requirements for cabling links and channels, d) the implementation requirements and options, e) the performance requirements for cabling components, f) the conformance requirements and verification procedures. Safety (e.g. electrical safety and protection, fire) and electromagnetic compatibility (EMC) requirements are outside the scope of this document, and are covered by other standards and by regulations. However, information given by this document can be of assistance.
3 Terms, definitions and abbreviated terms
3.1 Terms and definitions For the purposes of this document, the terms and definitions given in ISO/IEC 1 1 801 -1 and the following apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses: • IEC Electropedia: available at http://www.electropedia.org/ • ISO Online browsing platform: available at http://www.iso.org/obp 3.1 .1 computer room one or more spaces primarily dedicated to housing cabling and equipment used for electronics data storage, processing and networking 3.1 .2 computer room space area within the data centre that accommodates the data processing, data storage and telecommunications equipment that provides the primary function of the data centre 3.1 .3 equipment outlet fixed connecting device for terminating the zone distribution cabling and providing the interface to the equipment cord 3.1 .4 fixed zone distribution cable cable connecting the zone distributor to either the equipment outlet or, if present, the local distribution point 3.1 .5 intermediate distribution cable cable connecting the intermediate distributor to the zone distributor 3.1 .6 intermediate distributor distributor used to make connections between the main distribution cabling subsystem, intermediate distribution cabling subsystem, network access cabling subsystem and cabling subsystems specified in ISO/IEC 1 1 801 -1 and active equipment 3.1 .7 local distribution point connection point in the zone distribution cabling subsystem between a zone distributor and an equipment outlet 3.1 .8 local distribution point cable cable connecting a local distribution point to an equipment outlet 3.1 .9 local distribution point link transmission path between a local distribution point and the interface at the other end of the fixed zone distribution cable including the connecting hardware at each end 3.1 .1 0 main distribution cable cable connecting the main distributor to the intermediate distributor or the zone distributor 3.1 .1 1 main distributor distributor used to make connections between the main distribution cabling subsystem, network access cabling subsystem and cabling subsystems as specified in ISO/IEC 1 1 801 -1 and active equipment 3.1 .1 2 network access cable cable connecting the external network interface (or other distributors of the ISO/IEC 1 1 801 series) to the main distributor, intermediate distributor or zone distributor 3.1 .1 3 transition assembly assembly of cabled optical fibres and connectors, with an MPO connector on one end and simplex or duplex connectors on the other end 3.1 .1 4 zone distribution cable cable connecting the zone distributor to the equipment outlet(s) or local distribution point(s), where present 3.1 .1 5 zone distributor distributor used to make connections between the main distribution cabling subsystem, intermediate distribution cabling subsystem, zone distribution cabling subsystem, network access cabling subsystem, cabling subsystems specified in ISO/IEC 1 1 801 -1 and active equipment