ASME B16.40:2008 pdf download

admin
ASME B16.40:2008 pdf download

ASME B16.40:2008 pdf download Manually Operated Thermoplastic Gas Shutoffs and Valves in Gas Distribution Systems
(c) Leak test fluid shall be air or other gas. During leakage testing, there shall be no visible leakage (break- ing away or buildup of bubbles) as measured by the immersionor leakdetectionsolutionmethods. Ifimmersion is used, the depth from the water surface shall be no more than 12 in. (300 mm). Other means of leak detection may be used, provided they can be shown to be equivalent in leak detection sensitivity.
6.2 Production Testing
6.2.1 Shell Test. Each valve shall be tested at 4 psi ± 2 psi (0.28 bar ± 0.14 bar) and ata minimumof1.5 times the design pressure. The test pressure shall be applied to all pressure-containing areas of the valve (including stem seals and valve ends). This may require that the valve be in the partially open position. The shell test shall be conducted at a temperature of 73°F ± 15°F (23°C ± 8°C). The test fixturing shall not restrain the valve against any mode of failure or leakage. The minimum duration of each of the two shell tests shall be as shown in Table 1.
6.2.2 Seat Test. Each valve shall be seat closure tested at 4 psi ± 2 psi (0.28 bar ± 0.14 bar) and at a minimum of 1.5 times the valve design pressure. These pressures shall be applied successively on each side of the valve seat(s) to check the valve-sealing performance in both directions. The seat test shall be conducted at a temperature of 73°F ± 15°F (23°C ± 8°C). The seat test’s fixturing shall not restrain the valve against any mode of failure or leakage. The minimum duration of each portion of the test shall be as shown in Table 1.
6.3 Qualification Testing
6.3.1 OperationalTest. Itshall be demonstrated that each nominal size of each basic valve design is capable of successfully passing the seat leakage tests of para. 6.2.2, after having completed ten fully opened/closed cycles at 73°F ± 15°F (23°C ± 8°C). The valve shall be pressurized with air or other gas to the design pressure at one port with the other port open to atmosphere before opening on each cycle. At the start of each cycle, the operating torque shall be measured and not exceed those in Table 2 for −20°F (−29°C). 6.3.2 Temperature Resistance. It shall be demon- strated that each nominal size of each basic valve design is capable of being operated at temperatures of −20°F 3 ± 5°F (−29°C ± 3°C) and 140°F ± 5°F (60°C ± 3°C) without visible leakage to atmosphere and without affecting the internal seat-sealing performance of the valve. The method of test is as follows. A closed valve shall be cooled to a temperature of −20°F ± 5°F (−29°C ± 3°C) and held there for an 18-hr minimum. The valve shall then be pressurized with air or gas to a differential pres- sure across the seat equal to the valve design pressure. The valve shall then be opened against the applied- differential pressure, using a torque less than or equal to that of Table 2 at the −20°F (−29°C) values and then closed (no differential pressure across the seat required). The valve shall then be tested to meet the requirements of para. 6.2 while at −20°F (−29°C), except nonfreezing leak-detection agents shall be used. The valve shall then be heated to a temperature of 140°F ± 5°F (60°C ± 3°C) and held there for an 18-hr minimum. The closed valve shall then be pressurized with air or other gas to a differential pressure across the seat equal to the valve’s design pressure at 140°F (60°C). The valve shall then be opened against the applied-differential pressure using a torque less than or equal to that of Table 2 [140°F (60°C)] values and then closed (no differential pressure across the seat required). The valve shall then be tested to and meet the requirements of para. 6.2, while at 140°F (60°C).
6.3.3 Sustained-Pressure Test. Each basic valve design shall be subjected to the sustained-pressure tests described herein to evaluate the long-term pressure integrity of the valve shell and closure elements. All valves shall be in the open position for the Pressure- Boundary Test [see para. 6.3.3(a)] and in the closed posi- tion for the Closure Verification Test [see para. 6.3.3(b)]. For both PE and PA-11, Table 3 offers two choices of pressures and duration times for the sustained pressure test. The valve manufacturer may choose to test for 1,000 hr at the lower listed pressures, depending on valve DR, or for 170 hr at the higher listed pressures. Either choice is valid. The valve manufacturer is not required to perform both tests. The valves shall not fail, as defined in ASTM D 1598, when subjected to the sustained pressure test.
(a) Pressure-Boundary Tests. Six samples of each basic valve design shall be connected at both ends to thermo- plastic pipe of appropriate wall thickness of a length of at leastfive times its outside diameter or 20 in. (510 mm), whichever is less. These assemblies shall be subjected to a sustained-pressure test test as chosen from the sus- tained test pressures and minimum durations as listed in Table 3. The DRv for the valve shall be used in determining the test pressure. Failure of two of the six samples tested shall constitute failure in the test. Failure of one of the six samples tested is cause for a retest of six additional samples. Failure of one of the six samples in retest shall constitute failure in the test. Failure of a test sample shall be as defined in ASTM D 1598.